AEG ELFA SERIES MINI BREAKERS
E88S MINI CIRCUIT BREAKERS
(80A - 125A)

AEG ELFA E88S MINI CIRCUIT BREAKER GROUP

  • 80 Amp - 125 Amp - Rated (80 - 125 Amp Non-UL)
  • 35mm DIN Rail Mounted
  • Screw Torque to 5 N.m
  • Mechanical Endurance (10,000 operations)
  • Electrical Endurance (4,000) operations)
  • Current Limiting Design (Energy Limit Class 3)
  • Max. AC Volts
    • 277 / 480 V
  • Max DC Volts
    • (1P) 48 VDC
    • (2P) 110 VDC
  • Operating Temperature: from -25°C to +50°C according to IEC 60898
  • Thermal Operating Limit: (1.13 - 1.45 x In)
  • Storage Temperature
    • From -55°C up to +55°C
    • according to IEC 88 part 2-1
  • EN60947-2
  • VDE
  • CE
  • 3 Optional Trip Characteristics
    • B = 3-5 x Magnetic Release
    • C = 5-10 x Magnetic Release
    • D = 10-20 x Magnetic Release
Test Current
Tripping Time
Application
B
3 In
5 In
t ≥ 0.1s
t < 0.1s
Only for resistive
- Loads such as:
- Electrical heating
- Water Heater
- Stove
C
5 In
10 In
t ≥ 0.1s
t < 0.1s
Usual loads such as:
- Lighting
- Sockets
- Small Motors
D
10 In
20 In
t > 0.1s
t < 0.1s
Control and protection
of circuits having
important transient
inrush currents
(large motors)

 

DIMENSIONAL DATA
Dimensions Approx. mm (inch)
E881S, E882S, E883S - 80A to 125A

AEG E88S MINI CIRCUIT BREAKER DIMENSIONS
Click Image for Larger View

 
Contact Cal-Centron For Prices
 
AEG ELFA E880S MINI CIRCUIT BREAKER - 1 POLE
"B" TRIP (3-5 X In)
"C" TRIP (5-10 X In)
"D" TRIP (10-20 X In)
Amps
Number
Amps
Number
Amp
Number
80
E881SB080
80
E881SC080
80
E881SD080
100
E881SB100
100
E881SC100
100
E881SD100
125
E881SB125
125
E881SC125
125
E881SD125
 
E880S SERIES TWO POLE - MINI CIRCUIT BREAKERS (80 Amp - 125 Amp)
AEG ELFA E880S MINI CIRCUIT BREAKER - 2 POLE
"B" TRIP (3-5 X In)
"C" TRIP (5-10 X In)
"D" TRIP (10-20 X In)
Amps
Number
Amps
Number
Amp
Number
80
E882SB080
80
E882SC080
80
E882SD080
100
E882SB100
100
E882SC100
100
E882SD100
125
E882SB125
125
E882SC125
125
E882SD125
 
E880S SERIES THREE POLE - MINI CIRCUIT BREAKERS (80 Amp - 125 Amp)
AEG ELFA E880S MINI CIRCUIT BREAKER - 3 POLE
"B" TRIP (3-5 X In)
"C" TRIP (5-10 X In)
"D" TRIP (10-20 X In)
Amps
Number
Amps
Number
Amp
Number
80
E883SB080
80
E883SC080
80
E883SD080
100
E883SB100
100
E883SC100
100
E883SD100
125
E883SB125
125
E883SC125
125
E883SD125
 
 
 

Q: Where can I use AEG's (1077) approved mini breakers?
A: Practically anywhere supplemental protection is required. Motor loads, transformers, heating resistive loads, control circuits.

Q: Is there any minimum distance between circuit breakers?
A: You can mount AEG mini breakers side by side with each other. There is a recommendation of approx. 35mm (1.4") when mounting breakers above each other in a parallel plane.

Q: Do I need any additional upstream protection?
A: Local codes vary, however typically upstream protection is already provided via the primary plant & distribution panel (UL489 approved breaker).

Q: If I need a UL489 breaker for my application can you supply?
A: Refer to CBS Series Molded Case Circuit Breakers for a full line series of UL489 breakers from (15 amps - 600 Amps)

Please contact Cal-Centron for additional Information.