AEG ELFA SERIES MINI BREAKERS
E90S MINI CIRCUIT BREAKERS
(0.5A - 63A)

AEG ELFA E90S MINI CIRCUIT BREAKER GROUP

 

  • 0.5 Amp - 63 Amp - UL
  • 35mm DIN Rail Mounted
  • Screw Torque to 4.5 N.m
  • Mechanical Endurance (20,000 operations)
  • Electrical Endurance (10,000) operations)
  • Current Limiting Design (Energy Limit Class 3)
  • Wire Range - #2 AWG or 2 x #6 AWG (max.) #18 AWG (min.) - 35/2 x 16 m² Max.
  • Max. AC Volts
    • 277 / 480 V
  • Max DC Volts
    • (1P) 48 VDC
    • (2P) 110 VDC
  • Operating Temperature: from -25°C to +50°C according to IEC 60898
  • Thermal Operating Limit: (1.13 - 1.45 x In)
  • Shock Resistance (in x, y, z direction)
    • 20g with shock duration of 10ms (minimum 18 shocks)
    • 40g with shock duration of 5ms (minimum 18 shocks)
  • Vibration Resistance (in x, y, z direction)
    • 3g in frequency range 10 to 55Hz (operating time at least 30 minutes)
    • according to IEC 77 16.3 and DIN 40046 part 8
  • Storage Temperature
    • From -55°C up to +55°C
    • according to IEC 88 part 2-1
  • UL 1077 / CSA (File # E151139)
  • CE
  • IEC 60898 / 600947-2
  • CEBEC
  • VDE
  • KEMA
  • BS4293
  • IMQ
  • 3 Optional Trip Characteristics
    • B = 3-5 x Magnetic Release
    • C = 5-10 x Magnetic Release
    • D = 10-20 x Magnetic Release
Test Current
Tripping Time
Application
B
3 In
5 In
t ≥ 0.1s
t < 0.1s
Only for resistive
- Loads such as:
- Electrical heating
- Water Heater
- Stove
C
5 In
10 In
t ≥ 0.1s
t < 0.1s
Usual loads such as:
- Lighting
- Sockets
- Small Motors
D
10 In
20 In
t > 0.1s
t < 0.1s
Control and protection
of circuits having
important transient
inrush currents
(large motors)

 

DIMENSIONAL DATA
Dimensions Approx. mm (inch)
E91S, E92S, E93S - 0.5A to 63A (B, C Trip)

AEG E90S MINI CIRCUIT BREAKER DIMENSIONS
Click Image for Larger View

 
Contact Cal-Centron For Prices
 
AEG ELFA E90S MINI CIRCUIT BREAKER - 1 POLE
"B" TRIP (3-5 X In)
"C" TRIP (5-10 X In)
"D" TRIP (10-20 X In)
Amps
Number
Amps
Number
Amp
Number
-
-
0.5
E91SULC0.5
0.5
E91SULD0.5
-
-
1
E91SULC01
1
E91SULD01
-
-
2
E91SULC02
2
E91SULD02
-
-
3
E91SULC03
3
E91SULD03
-
-
4
E91SULC04
4
E91SULD04
5
E91SULB05
5
E91SULC05
5
E91SULD05
6
E91SULB06
6
E91SULC06
6
E91SULD06
10
E91SULB10
10
E91SULC10
10
E91SULD10
13
E91SULB13
13
E91SULC13
13
E91SULD13
15
E91SULB15
15
E91SULC15
15
E91SULD15
16
E91SULB16
16
E91SULC16
16
E91SULD16
20
E91SULB20
20
E91SULC20
20
E91SULD20
25
E91SULB25
25
E91SULC25
25
E91SULD25
30
E91SULB30
30
E91SULC30
30
E91SULD30
32
E91SULB32
32
E91SULC32
32
E91SULD32
40
E91SULB40
40
E91SULC40
40
E91SULD40
50
E91SULB50
50
E91SULC50
50
E91SULD50
60
E91SULB60
60
E91SULC60
60
E91SULD60
63
E91SULB63
63
E91SULC63
63
E91SULD63
 
E90S SERIES TWO POLE - 10KA MINI CIRCUIT BREAKERS (0.5 Amp - 63 Amp)
AEG ELFA E90S MINI CIRCUIT BREAKER - 2 POLE
"B" TRIP (3-5 X In)
"C" TRIP (5-10 X In)
"D" TRIP (10-20 X In)
Amps
Number
Amps
Number
Amp
Number
-
-
0.5
E92SULC0.5
0.5
E92SULD0.5
-
-
1
E92SULC01
1
E92SULD01
-
-
2
E92SULC02
2
E92SULD02
-
-
3
E92SULC03
3
E92SULD03
-
-
4
E92SULC04
4
E92SULD04
5
E92SULB05
5
E92SULC05
5
E92SULD05
6
E92SULB06
6
E92SULC06
6
E92SULD06
10
E92SULB10
10
E92SULC10
10
E92SULD10
13
E92SULB13
13
E92SULC13
13
E92SULD13
15
E92SULB15
15
E92SULC15
15
E92SULD15
16
E92SULB16
16
E92SULC16
16
E92SULD16
20
E92SULB20
20
E92SULC20
20
E92SULD20
25
E92SULB25
25
E92SULC25
25
E92SULD25
30
E92SULB30
30
E92SULC30
30
E92SULD30
32
E92SULB32
32
E92SULC32
32
E92SULD32
40
E92SULB40
40
E92SULC40
40
E92SULD40
50
E92SULB50
50
E92SULC50
50
E92SULD50
60
E92SULB60
60
E92SULC60
60
E92SULD60
63
E92SULB63
63
E92SULC63
63
E92SULD63
 
E90S SERIES THREE POLE - 10KA MINI CIRCUIT BREAKERS (0.5 Amp - 63 Amp)
AEG ELFA E90S MINI CIRCUIT BREAKER - 3 POLE
"B" TRIP (3-5 X In)
"C" TRIP (5-10 X In)
"D" TRIP (10-20 X In)
Amps
Number
Amps
Number
Amp
Number
-
-
0.5
E93SULC0.5
0.5
E93SULD0.5
-
-
1
E93SULC01
1
E93SULD01
-
-
2
E93SULC02
2
E93SULD02
-
-
3
E93SULC03
3
E93SULD03
-
-
4
E93SULC04
4
E93SULD04
5
E93SULB05
5
E93SULC05
5
E93SULD05
6
E93SULB06
6
E93SULC06
6
E93SULD06
10
E93SULB10
10
E93SULC10
10
E93SULD10
13
E93SULB13
13
E93SULC13
13
E93SULD13
15
E93SULB15
15
E93SULC15
15
E93SULD15
16
E93SULB16
16
E93SULC16
16
E93SULD16
20
E93SULB20
20
E93SULC20
20
E93SULD20
25
E93SULB25
25
E93SULC25
25
E93SULD25
30
E93SULB30
30
E93SULC30
30
E93SULD30
32
E93SULB32
32
E93SULC32
32
E93SULD32
40
E93SULB40
40
E93SULC40
40
E93SULD40
50
E93SULB50
50
E93SULC50
50
E93SULD50
60
E93SULB60
60
E93SULC60
60
E93SULD60
63
E93SULB63
63
E93SULC63
63
E93SULD63
 
 
 

Q: Where can I use AEG's (1077) approved mini breakers?
A: Practically anywhere supplemental protection is required. Motor loads, transformers, heating resistive loads, control circuits.

Q: Is there any minimum distance between circuit breakers?
A: You can mount AEG mini breakers side by side with each other. There is a recommendation of approx. 35mm (1.4") when mounting breakers above each other in a parallel plane.

Q: Do I need any additional upstream protection?
A: Local codes vary, however typically upstream protection is already provided via the primary plant & distribution panel (UL489 approved breaker).

Q: If I need a UL489 breaker for my application can you supply?
A: Refer to CBS Series Molded Case Circuit Breakers for a full line series of UL489 breakers from (15 amps - 600 Amps)

Please contact Cal-Centron for additional Information.